NJ300 - Digital Input/Output Hybrid Module
Category:
- Product Description
- Performance Parameters
-
Digital input/output hybrid module, 16-point input 24VDC, 16-point output 24VDC.
The DXM301-3201 digital input/output module has the following features:
16-point D0 output characteristics:
16 output channels, with isolation, grouped in sets of 16, with one common terminal:
Output type: 24VDC transistor, source-type output:
The output is protected by a fuse and can automatically protect the module in case of overload.
In case of a fault, set the function to 0 or 1, or retain the last function.
16-point DI input characteristics:
16 input points, with 8 points sharing a common terminal each; source and drain compatible signal input.
Rated input voltage: 24VDC;
Suitable for switches and 2/3/4-wire proximity switches:
Each digital input measurement point can have its filter time set via software from 0 to 2500 ms (in 10-ms increments).
Smart module with self-diagnostic function; when a fault occurs during module operation, it can automatically reset and restart.
No hardware configuration is required; after startup, the CPU module automatically loads its parameters.
Each channel has independent electrical isolation, ensuring that a signal on one channel will not affect the normal operation of the entire module even in the presence of strong electrical interference.
Supports hot-swapping. -
Model
DXM301-3201
Number of channels
Output 16 points
Enter 16 points
Module load
450mA/5V
200mA/5V
Output/Input Type
Transistor, source-type output
Source-Drain Common Input
Output voltage
24VDC
-
Channel continuous load current
0.5A
-
Maximum load current of the channel (0~40℃)
0.6A, 100ms
-
Minimum load current of the channel (0~40℃)
5mA
-
Maximum load current of the channel's public end
3A
-
Switching frequency
Resistive load
Inductive load100Hz
0.5 Hz-
-Signal voltage
“1” signal voltage
“0” signal voltage-
-14~30V
-30~5VResponse Time (ON)
-
≤0.5 ms
Response Time (0FF)
-
≤0.5 ms
Operating temperature
-25~65℃
Status display
Each channel has a green LED indicator.
Self-diagnosis function
There is
Insulation testing
500VDC
Channel isolation
Between channels
Between the channel and the backplaneThere is
Yes, optoelectronic isolation.Power consumption
3.25W
Weight (g)
370
Width x Height x Depth (mm)
32x110x97
Related Downloads
Related Products
Product Inquiry