Welcome to the offical website of Atekon Automation Technology Co.,Ltd
Product
Serial port module type |
CMM401-0103 |
Order number |
400CMM4010103 |
Power consumption |
2.0W/5V |
Current consumption |
400mA/5V |
Number of bus interfaces |
1 |
Bus interface type |
Profibus DP slave |
Support communication baud rate |
4800~12Mbps |
Interface isolation |
Photoelectric isolation 2500V rms |
Programming Drive |
Manufacturers provide GSD files |
Weight |
220g |
Dimensions (W×H×D) |
40mm×145mm×158mm |
*The information provided in this article is just a general description and feature introduction of the product. The content in this article may change with the further development of the product, and the right of interpretation belongs to Nanda Automation Technology Co., Ltd.
Profibus DP slave module
CMM401-0103
Features
Standard PROFIBUS-DP slave interface: DP-V0/V1 protocol, in line with IEC61158 and Chinese national standard GB/T20540-2006: Fieldbus for measurement and control of digital data communication industrial control system Part 3
The baud rate can be set, the maximum baud rate is 12M.
Up to 30 slave stations can be connected on the Profibus bus.
Maximum expansion I/O module: 32-point DI/32-point DO module ≤32 blocks; 16-point AI module ≤7 blocks; 4-point AO module ≤7 blocks.
Intelligent module, powerful self-diagnosis function, the module can automatically reset and restart the unique data safety output function when the module fails, so that the control device has a higher safety function.
Comprehensive LED indicators: comprehensive LED indications of power supply, module activation, module operation, fault, PROFIBUS bus operation and fault.
Support hot swap.
Module hardware settings and external interfaces
1. DP slave address coding switch
The module provides two decimal rotary coding switches S1 and S2, DP slave address = S1*1+S2*10, which needs to be set correctly before power on.
2. Two-digit DIP switches K1 and K2
K1: The system is reserved for updating firmware. Before the module is powered on, please confirm that K1 is in the OFF position.
K2: Optional switch for the 120-ohm terminal resistance of the bus cable. The OFF position indicates that the terminal resistance is not connected, and the ON position indicates that the terminal resistance is connected.
3. DP communication interface
DP-S: Standard SUBDB9 Female interface, the interface lead definition is shown in the following table:
NO. |
Pin definition |
NO. |
Pin definition |
NO. |
Pin definition |
1 |
SHIELD optional |
4 |
CNTR_P |
7 |
P24 |
2 |
M24 optional |
5 |
DGND |
8 |
RS485_N |
3 |
RS485_P |
6 |
P5V |
9 |
NC |
Note: The NC table is not connected.
Due to physical and electrical performance limitations, the maximum number of modules that can be connected to the Profibus bus is 30. Please pay attention to this limitation when configuring. If the number of slave stations must be greater than 30, please add profibus relay equipment.
*The information provided in this article is just a general description and feature introduction of the product. The content in this article may change with the further development of the product, and the right of interpretation belongs to Nanda Automation Technology Co., Ltd.
底部二维码
Welcome to Atekon
Technology official Wechat
底部联系方式
Address: Floor8,BuildingD,Cloud Security City,No.19 Ning shuang Road,Yuhuatai District,Nanjing
Production Center: No. 219 Qingshuiting West Road, Jiangning District, Nanjing City
Telephone: 025-68530188 (Switchboard)
Fax: 025-68530178
Service Hotline: 400-025-0150
Technical support: 025-68530179
底部备案号
Atekon Technology Co.,Ltd Record number: 苏ICP备09042342号-1